Duct Protection & Dampers
Duct wrap, board enclosure and dampers — the whole opening, not the visible product.
Overview
In short: Fire Rated Systems installs and records duct protection where ductwork crosses a fire-rated wall or floor in Western Australia: duct wrap, board enclosure, fire dampers and smoke dampers, plus the supports, joints, access doors and the opening itself.
A duct crossing a fire-resisting element is not one item. It is the duct, the protection on it, the supports, the joints, the access doors, the opening in the wall and, where there is one, the damper sitting in it. Any of those can be the reason the system does not hold. FRS builds and records all of them.
Duct wrap and board enclosure
A fire-resisting duct system is more than insulation wrapped around sheet metal. The duct construction, the protection system, orientation, supports, joints, access doors, penetrations and the tested or assessed arrangement all matter. Adding insulation to ordinary ductwork does not create that system.
It also matters which way the fire is expected to come. A duct tested for fire outside the duct is not evidence for a duct where the fire can start inside it — kitchen exhaust and smoke spill ducts are the usual cases — and the two are protected differently. Swapping one for the other because the FRL number matches is a mistake that generally surfaces at handover, when the certification does not.
Wrap or board is not a preference. Duct duty, geometry, the space available, the supports, access requirements, the surrounding construction and which arrangements the evidence covers decide it between them.
Fire dampers
A fire damper closes an opening where a duct passes through a fire-resisting building element, and closes on heat — usually through a thermal release device such as a fusible link. That link is the part to look for on site, and the part most often painted over, tied back, or replaced with the wrong temperature rating.
Most damper defects are not in the damper. They are in the construction immediately around it: whether the damper sits in the plane of the element or within the offset its evidence allows, whether the retaining angles are the ones specified and fixed the way the evidence requires, whether the gap between sleeve and opening is fire-stopped to a supported detail, whether the duct-to-damper connection is a breakaway connection where one is required, whether there is an access panel big enough and close enough to inspect and reset the damper, and orientation — a damper tested vertically is not evidence for a horizontal installation.
A label on the damper says nothing about any of that.
Smoke dampers
A smoke damper does a different job. It controls the movement of smoke and is generally driven by the detection or control system rather than by heat alone, because smoke moves well before the temperature at the damper rises. Where a damper has a smoke-control duty it sits inside the system requirements for that installation and has to be commissioned as part of it.
A damper being present in an opening does not tell you which requirement it was installed to meet. That is settled by the project documents and the commissioning record, not by looking at it.
What FRS can take on
- Duct wrap — fire-resisting duct protection installed to the tested or assessed arrangement, including supports, joints and access provisions.
- Board enclosure to ducts — rigid board systems where the duct duty, geometry or access makes boarding the supported answer.
- Fire dampers — installation at the fire-rated boundary, with the opening, retaining angles, breakaway connection and access panel built to the supported system.
- Smoke dampers — installation of the damper and the fire-rated boundary around it, coordinated with whoever holds the control and commissioning scope.
- Rectification — existing duct protection and damper installations, identified and brought back to a system that stands up.
- Inspection and recording — condition, location, system and evidence captured against each item.
- A written scope line — we set out in writing which parts of the damper installation are ours and which sit with the mechanical or commissioning contractor, so it is agreed before site rather than discovered at handover.
Technical library
Duct, damper and transit guides.
How often do fire and smoke dampers need testing in Western Australia?
In Western Australia, fire dampers are serviced to the Australian Standard AS 1851—2012. At least 20% of a building's fire dampers are inspected and tested every year, so every damper is checked within five years. Smoke dampers are tested every year. Fusible links are replaced every 20 years. If too many dampers in the yearly sample fail, every damper in the building has to be inspected within the next 12 months.
Scott CunninghamCan new cables be added to an existing cable transit?
Often yes. Being re-enterable is the point of a cable transit. But it only works within what the installed system allows. You need to know which system it is, whether it has spare capacity, and whether the new cables fit the inserts or modules that system was tested with. If the transit is opened, packed with the wrong parts or overfilled, it stops matching its evidence. At that point it is no longer a maintainable transit. It is an undocumented penetration that someone will have to investigate and fix later.
Scott CunninghamWhat is a cable-transit system?
A cable-transit system is a framed opening that carries cables through a fire-resisting wall or floor and keeps the fire separation intact. It is built so cables can be added or removed later without rebuilding the whole seal. Most use a frame fixed into the wall or floor, filled with modules, inserts or packers sized to each cable, then closed so the parts press tight around the cables. It only performs within what its tested system permits: the right parts, the right fill and the right closing method.
Scott CunninghamWhat is the difference between a fire damper and a smoke damper?
A fire damper stops fire passing along a duct where it goes through a fire-resisting wall or floor. It usually closes on heat, often when a fusible link melts and releases the blade. A smoke damper controls the movement of smoke through the ductwork. It is usually opened or closed by a detection or control system, not by heat alone. A combination fire and smoke damper does both jobs. Which one an opening needs depends on the building design and the system it serves. Seeing a damper in a duct does not tell you which requirement it was installed to meet.
Scott CunninghamWhat is the difference between a tested system and a product?
A product is a material or component: a sealant, a collar, a wrap, a board, a damper. A tested or assessed system is the complete configuration that product was fire tested or assessed in. That covers the wall or floor type, the service, the opening size, the depth of sealant, the backing, the fixings and the supports. The fire rating belongs to the system, not the tin or the box. Buying the right product does not prove the installation matches the system evidence. Only the installed condition, compared against that evidence, can show that.
Scott CunninghamWhat makes a fire-resisting duct system different from ordinary ductwork?
Ordinary ductwork just moves air. A fire-resisting duct system is a tested or assessed construction that keeps fire out of the duct, or keeps fire inside it, for the required time. The duct, its protection, the joints, the hangers and supports, the access openings and the points where it passes through walls and floors all work together as one system. Wrapping ordinary ductwork in insulation does not create that system. The whole arrangement has to match evidence for the duct size, duty and fire direction.
Scott CunninghamWhat should be checked around a fire damper installation?
Check the damper itself, the opening it sits in, how it is fixed, how the duct connects to it, whether there is access to it, which way it is installed, and, where it is linked to controls, that it responds to them. A fire damper only works as part of its installation. The label on the damper tells you what the damper is. It says nothing about the gap around it, the fixings, the duct connection or whether anyone can reach it to test it. Each of those has to match the evidence for that damper in that wall or floor.
Scott CunninghamQuestions
Frequently asked questions
- Is duct wrap the same as a fire-rated duct?
- Not automatically. A wrap is one component of a tested or assessed duct protection system. The duct, supports, joints, access and installation details matter as well.
- Does every duct through a fire wall need a fire damper?
- Not necessarily — it depends on the building design, the duct function and what the project documentation calls for. Send us the mechanical and fire drawings and we will tell you what is actually required.
- Who commissions the damper?
- That has to be clear in the project scope before anyone is on site. We install and record the damper and the fire-rated boundary around it; actuation, control wiring and commissioning stay with the mechanical, electrical or commissioning contractor. We will say so in writing rather than leaving it to be discovered at handover.