Ducts, dampers & transits · Servicing
How often do fire and smoke dampers need testing in Western Australia?
In Western Australia, fire dampers are serviced to the Australian Standard AS 1851—2012. At least 20% of a building's fire dampers are inspected and tested every year, so every damper is checked within five years. Smoke dampers are tested every year. Fusible links are replaced every 20 years. If too many dampers in the yearly sample fail, every damper in the building has to be inspected within the next 12 months.
The UK annual-test rules and the American four-year rules that come up in searches do not apply to a building in Western Australia.
What a damper test involves on site
A fire damper sits inside the ductwork where it passes through a fire-rated wall or floor. When it gets hot, it snaps shut and stops fire travelling through the duct. A smoke damper closes on a signal from the fire alarm to stop smoke moving through the system.
A test is more than a look through the access panel:
- Find it. Locate the damper against the asset register and confirm it can actually be reached.
- Look at it. Check the blades, frame, fixings, the seal to the wall or floor, and for corrosion.
- Drop it. Release it the way a fire would, and confirm it closes fully and latches.
- Reset it. Re-open it and leave it ready to work again.
- Record it. Location, result, photographs, and anything that needs fixing.
The damper is only part of the fire separation. The opening around it, the duct protection and the access panel all have to hold as well.
How often, by damper type
| What | How often under AS 1851—2012 | Clause |
|---|---|---|
| Fire dampers | At least 20% inspected and tested each year, all within 5 years | 13.4.1.4 |
| Fire dampers, when too many fail | Every damper in the building within 12 months | 13.4.1.4 |
| Smoke dampers | Tested and recorded every year | 13.4.2.9 |
| Fusible links | Replaced every 20 years | Table 13.4.14 |
A building with 80 fire dampers therefore has at least 16 tested every year, and all 80 over five years.
Why WA building owners need it
Under Regulation 48A of the Building Regulations 2012, the owner of a Class 2 to Class 9 building in Western Australia must keep its safety measures, including building fire integrity, performing to the standard the building was approved to. Fire dampers are part of that fire integrity. A damper nobody has tested is one the owner cannot show is working.
Most advice online about damper testing is written for the UK, where British Standards set yearly testing, or the United States, where American codes set a test one year after installation and then every four or six years. Neither applies to a building in Perth, Bunbury, Kalgoorlie, Geraldton or the Pilbara. In WA, the routine is AS 1851—2012.
The owner's duty is covered in more detail in What does a WA building owner have to do about passive fire?
What we find most often
- Dampers that cannot be reached: no access panel, or a ceiling built over it.
- Dampers painted shut, or jammed with dust and debris.
- Fusible links that are missing, painted over or the wrong rating.
- Gaps around the damper where it meets the wall or floor.
- No register, so nobody knows how many dampers the building has.
What changes the answer
- Damper type. Fire, smoke or combined dampers each have their own routine.
- Too many failures. A failed sample moves the whole building to a full inspection.
- No asset register. Building the register comes first, because the 20% sample is a share of a known total.
- The building's approval. The fire engineering report or performance solution can set requirements beyond the standard.
What to do next
- Find out how many dampers the building has and where they are.
- Check when each was last tested, and whether the records exist.
- Book the yearly 20% cycle, plus yearly smoke damper tests.
- Fix access problems first, because a damper you cannot reach cannot be tested.
Fire Rated Systems tests, repairs and records fire and smoke dampers across Perth and regional Western Australia.
Questions owners ask
How often do fire dampers need testing in WA?
At least 20% every year under AS 1851—2012, so every damper is tested within five years.
How often are smoke dampers tested?
Every year.
What happens if dampers fail?
If too many in the yearly sample fail, every damper in the building is inspected within 12 months.
When are fusible links replaced?
Every 20 years.
Do UK or US damper rules apply in WA?
No. In Western Australia the routine is AS 1851—2012.
General information, not advice on a specific building. Requirements in a fire engineering report or performance solution for your building may differ.