Across every service · Building owners

What does a WA building owner have to do about passive fire?

Short answer

If you own an existing commercial, industrial or apartment building in Western Australia, you must keep its passive fire protection working. Regulation 48A of the Building Regulations 2012 puts that duty on the owner, and it is a standing duty — it does not wait for an inspection, a sale or a refurbishment to switch on. The standard your building has to meet is the one it was approved to, not today's National Construction Code.

Passive fire protection means the fire doors, sealed service penetrations, fire-rated walls and floors, protected steel and fire dampers that hold fire and smoke in one part of a building. Western Australian law calls it building fire integrity.

What the law actually says

The chain runs from the Building Act 2011 to the Building Regulations 2012. Regulation 48A says the owner of an existing Class 2 to Class 9 building must ensure the building's safety measures remain capable of performing to the standard in the relevant building standards for each part of it.

  • Who it applies to: the owner. Not the tenant, not the facility manager, not the last contractor.
  • Which buildings: Class 2 to Class 9 — apartments, offices, shops, factories, warehouses, hospitals, schools, aged care and public buildings. Houses (Class 1) and sheds (Class 10) sit outside it.
  • What it covers: "safety measures", which the regulations define to include building fire integrity, alongside means of egress and automatic fire detection.
  • The penalty: a fine of $5,000.

Passive fire is not an optional extra to the sprinklers and alarms. It sits in the same defined list.

Which standard your building is held to

Not the current NCC. The regulations define "relevant building standards" as the edition of the Building Code named in the certificate of design compliance for the most recent building permit for that part of the building. Failing that, it is what applied at the last building licence, or when it was built.

  • A building finished in 1998 and never altered is measured against what applied in 1998.
  • A floor refitted under a 2019 permit is measured against the 2019 edition.
  • One building can carry several editions, one for each part.

This usually works in the owner's favour. A defect list that says an older building "does not meet NCC 2025" is often measuring it against a standard it was never required to meet. That is why a proper inspection starts with the building's approval history. More on this in Which NCC edition applies to my project?

What WA does not require

Much of what comes up when you search this question is written for New South Wales. It talks about an Annual Fire Safety Statement. That is a NSW requirement. Western Australia has no equivalent annual statement under the Building Regulations 2012.

That does not make WA lighter. The Regulation 48A duty is continuous rather than annual, and there is no form to lodge that tells you when you are done. The owner has to be able to show the building's safety measures still perform, whenever someone asks.

What it means in practice

The law sets the duty but not the method. In practice, an owner who can show the duty is met has five things:

  1. An asset register. Every fire door, sealed penetration, damper and fire-rated element, with its location. Without one there is no way to say what "working" means.
  2. The approval history. The permits for each part of the building, so you know which edition applies where.
  3. Routine service of fire and smoke doors and dampers to AS 1851—2012. That standard sets the routine for those assets.
  4. Inspection of barriers and penetration seals. AS 1851 does not cover them, so they are checked against the asset register and the test evidence behind each system.
  5. Records. What was inspected, what was found, what was fixed, and what is still open, with photographs.

The usual failures are quiet ones. A door that no longer latches. A seal painted over. A penetration opened for a new cable and never made good. None of it sets off an alarm.

What changes the answer

  • Building class. Regulation 48A covers Class 2 to 9. A house or a shed is outside it.
  • Strata buildings. The owner is the strata company for common property. Fire doors to individual apartments often sit on the boundary between common property and the lot, so the by-laws and the strata plan decide who is responsible for which door.
  • Leased buildings. The legal duty stays with the owner. A lease can pass the cost or the work to the tenant, but it does not move the duty in law.
  • A building with no records. The duty still applies. The first job is building the asset register, not waiting until one exists.

What to do next

  1. Find the building permits for each part of the building, or ask your building surveyor.
  2. Check whether an asset register exists for the passive fire. If it does not, that is the first job.
  3. Book routine service for the fire doors and dampers, and an inspection of the penetrations and barriers against the register.
  4. Keep every report, photo and certificate in one place the next owner or inspector can find.

We can do any of these, including a free first look at the building.

Questions owners ask

Is passive fire protection a legal requirement in WA?

Yes. For Class 2 to 9 buildings, Regulation 48A of the Building Regulations 2012 requires the owner to keep building fire integrity performing to the relevant standard.

Does my older building have to meet the current NCC?

No. It is held to the edition named in its most recent building permit for that part, or what applied when it was built.

Does WA need an Annual Fire Safety Statement like NSW?

No. That is a NSW requirement. WA's duty is continuous instead.

What is the penalty?

A fine of $5,000 under Regulation 48A.

Who is responsible in a leased building?

The owner. A lease can pass on the cost or the work, but not the legal duty.

General information about the Western Australian regulatory framework, not legal advice. Your building surveyor or a lawyer is the right person for advice on your own building. Source: Building Regulations 2012 (WA), regulations 3A and 48A, consolidated version on legislation.wa.gov.au.