Short answer

In Western Australia, fire doors and smoke doors are serviced to the Australian Standard AS 1851—2012. Hinged and pivoted fire doors and smoke doors are inspected and tested every six months. Sliding fire doors get a quick closing check every three months as well as the full six-monthly service. Entry doors to private apartments can go to a yearly service. Each six-monthly visit is allowed to run up to one month early or late. The building owner carries the duty to keep the doors working under Regulation 48A of the Building Regulations 2012. The yearly and quarterly rules that come up in searches are mostly from the UK or New South Wales and do not set the routine for a WA building.

The schedule at a glance

Door type How often Main check
Hinged or pivoted fire door Every 6 months Full inspection, operation test and survey
Hinged or pivoted smoke door Every 6 months Full inspection, operation test and survey
Sliding fire door Every 3 months Door closes fully from fully open and from part open
Sliding fire door Every 6 months Full inspection, operation test and survey
Hinged fire door that is the entry door to a private apartment Can be extended to yearly Full inspection, operation test and survey
Fire shutter Every year Full inspection, operation test and survey
Fire-rated glazing Every year Inspection, routine service and survey

The yearly option for apartment entry doors covers the door from the corridor into a private apartment only. Corridor, stair and plant room doors in the same building stay six-monthly. Many owners keep apartment entry doors on six-monthly anyway, because they are the doors most often damaged, propped or fitted with new locks.

How much leeway there is on dates

AS 1851 builds in a tolerance, so a service does not fail just because it fell on a different week:

  • Three-monthly: plus or minus 10 working days.
  • Six-monthly: plus or minus one month.
  • Yearly: plus or minus two months.

The tolerance is for scheduling, not catching up. A door last serviced eight months ago is overdue.

What a six-monthly check covers

A proper service is more than a walk past. On each door the technician should:

  • Identify it. Match the door to the asset register and its location, and read the tag or label on the door and frame.
  • Look at the leaf and frame. Damage, holes, warping, loose frames, unapproved fixings, signs of past repairs.
  • Check the gaps. Measure the gaps at the sides, top and bottom against the tested limits. See What do gaps around a fire door mean?
  • Check the hardware. Hinges, closer, latch, handles, locks and any added access control. The hardware has to be what the tested doorset allows.
  • Check the seals. Smoke seals and intumescent seals present, intact and not painted over. See Do fire doors need seals?
  • Test it. Open the door fully and let it go. It must close and latch on its own, every time.
  • Test any hold-open or operator. It must release and let the door close when the fire alarm activates.
  • Survey the area. Look for changes since the last visit that affect the door: a new wall, a new lock, a door now wedged open, storage in the way.
  • Record it. Pass or fail, what failed, a photo, and what happens next.

What usually fails

  • Doors wedged or propped open, or a hook added to hold them.
  • Closers that no longer latch the door, or that have been disconnected.
  • Gaps grown too wide after floor coverings changed.
  • Smoke seals missing, damaged or painted.
  • New locks, card readers or kick plates fitted without checking the doorset.
  • Holes from old hardware left open.
  • Tags painted over or missing.

Most of these are cheap to fix when found early. Left for years, they turn into a door replacement.

How this fits with WA law

The Building Regulations 2012 set the duty but not the method. Regulation 48A says the owner of an existing Class 2 to 9 building must keep its safety measures, including building fire integrity, performing to the standard the building was approved to. Routine service of fire and smoke doors to AS 1851—2012, with records, is how an owner shows that duty is met. More in What does a WA building owner have to do about passive fire?

WA has no annual fire safety statement like New South Wales. That does not mean less checking. It means there is no form to lodge, and the owner has to be able to show the doors work whenever someone asks: an insurer, a buyer, a building surveyor or the local government.

What changes the answer

  • What the building approval says. Some buildings have conditions or a fire engineering report that set extra checks for particular doors. Those apply on top of AS 1851.
  • Older buildings. The routine is usually set to AS 1851—2012 today, but the door itself is judged against the standard it was approved to.
  • Strata buildings. Apartment entry doors often sit between common property and the lot. The strata plan and by-laws decide who pays for which door.
  • Heavy use. Doors in hospitals, schools, car parks and busy corridors wear faster. Six months is the minimum, not a target.

What to do next

If you are not sure when your fire doors were last serviced, start with the records. If there are none, the first job is an asset register: every fire and smoke door, where it is, and what it is. FRS inspects, services and repairs fire doors and smoke doors across Perth and regional Western Australia, and the first site look is free.

Questions people ask

How often do fire doors need to be inspected in WA?

Every six months for hinged and pivoted fire doors and smoke doors, under AS 1851—2012. Sliding fire doors also get a three-monthly closing check.

Do fire doors need inspecting every year or every six months?

Every six months for most fire doors. Entry doors to private apartments, fire shutters and fire-rated glazing can be serviced yearly.

Are quarterly fire door inspections required?

Only for sliding fire doors, which get a three-monthly check that they close fully. Hinged fire doors are six-monthly.

Who is responsible for fire door inspections in WA?

The building owner, under Regulation 48A of the Building Regulations 2012. For strata buildings, that is usually the strata company for common property doors.

Can our maintenance person check the fire doors?

They can look for obvious problems between services, like wedges and broken closers. The six-monthly service should be done by someone who knows fire doorsets and can record it to AS 1851.

What happens if a fire door fails inspection?

It is recorded with what failed and what is needed. Small items like closers and seals are usually fixed on the spot or soon after. A door that cannot be brought back to its tested doorset may need replacing.

Do the UK fire door rules apply in Australia?

No. The UK quarterly and annual rules are set by UK law. A WA building is serviced to AS 1851.

General information, not legal advice. Your building surveyor is the right person to confirm what applies to your building.