Openings · Curtains & shutters
Fire curtains and smoke curtains: what they are, and how they are kept working in WA
A fire curtain closes an opening so the wall around it keeps its fire resistance level, the same job as a fire door or fire shutter. A smoke curtain does not stop fire. It controls where smoke goes: it holds smoke up above head height, keeps it off an escape route, or steers it to where the smoke exhaust can take it away. Both usually sit rolled up out of sight and drop on a signal from the fire detection system. In Australia they are routinely serviced six-monthly and yearly under AS 1851-2012, and in Western Australia the building owner has a legal duty to keep them working.
Fire curtain or smoke curtain: the difference
- Fire curtain: closes an opening in a fire-rated wall. It is fire tested to AS 1530.4 and carries a fire resistance level, like a door or shutter does. If the wall needs to hold fire for two hours, the curtain in it has to as well.
- Smoke curtain: a barrier that controls the movement of smoke inside a space. It is not there to hold a fire resistance level.
- Why it matters: they can look identical rolled up in a ceiling. They are not interchangeable. If the fire engineering report calls for one and the drawings show the other, it needs sorting out before anything is ordered.
Where you find them
- Shopping centre and office atriums and voids, where smoke would otherwise fill every level.
- Lift lobbies and openings where the architecture will not take a door.
- Large open-plan floors that are too big to divide with walls.
- Retail frontages, serveries and counters opening onto a mall or corridor.
- Car parks and loading areas, as fixed downstands under the slab.
Some smoke curtains are fixed and always down, called static curtains or downstands. Most fire curtains and many smoke curtains are automatic: rolled up in a headbox and released on alarm.
How they get approved
Fire curtains are tested to AS 1530.4, the same fire test used for doors and shutters, and given a fire resistance level.
Smoke curtains have no Australian product standard of their own. They are usually tested to the European smoke barrier standard EN 12101-1 and come into a project through the fire engineering report, as part of a Performance Solution under the National Construction Code. That report sets where the curtain goes, how far down it comes, and what makes it drop.
That makes the fire engineering report the document to keep with the curtain. Without it, nobody can say whether the curtain is doing what it was approved to do.
What goes wrong
- Wrong drop height. Many smoke curtains are designed to stop part of the way down, holding smoke above people while they walk out underneath. One that drops to the wrong height has changed the escape route, not just failed to help.
- Something parked underneath. Shelving, pallets, display stands or a new counter under the curtain line mean it cannot close.
- Never dropped since handover. Guides fill with dust and paint, the motor and brake sit unused, and nobody knows if it works until it has to.
- Linked to the wrong zone. The curtain must drop on the right detector, in the right zone, in the right time. A fit-out that rezones the detection can break that without anyone touching the curtain.
- Fit-out damage. New ceilings, bulkheads and services cut around the headbox or side guides, or a gap left between the curtain and the slab above.
- Back-up power. Many automatic curtains carry a battery back-up so they still drop in a power failure. Flat or old batteries are a common finding.
How often they are checked
| What | Routine service | Standard |
|---|---|---|
| Fire curtains and smoke curtains | Six-monthly and yearly | AS 1851-2012, clauses 13.4.1.11 and 13.4.1.12 |
| Fire shutters | Yearly | AS 1851-2012, clause 12.4.5 |
A proper service drops the curtain the way it would drop in a fire, measures how far it comes down and how long it takes, checks it resets, and writes the result down. A look from the floor does not tell you any of that.
Under Regulation 48A of the Building Regulations 2012, the owner of a Class 2 to 9 building in Western Australia must keep its safety measures, including building fire integrity, performing to the standard the building was approved to. Curtains and shutters are part of that. More in What does a WA building owner have to do about passive fire?
What to check as an owner or facility manager
- Do you have a list of every fire curtain, smoke curtain and shutter in the building, and where each one is?
- Do you have the fire engineering report that called for the smoke curtains?
- When was each one last dropped and timed, and is there a record?
- Is anything stored or built under any of them?
- Has a fit-out changed the ceiling, the detection zones or the space beneath since they were installed?
If you cannot answer one of these, that is where to start. Fire Rated Systems supplies, installs, commissions and services fire shutters, fire curtains and smoke curtains across Perth and regional Western Australia.
Questions owners ask
Is a smoke curtain the same as a fire curtain?
No. A fire curtain holds a fire resistance level across an opening. A smoke curtain controls where smoke goes.
How often do fire and smoke curtains need servicing?
Six-monthly and yearly routine service under AS 1851-2012.
Can I replace a smoke curtain with a different one?
Only if it matches what the fire engineering report requires. Check with the fire engineer or building surveyor first.
Can I put shelving under a curtain?
No. The space under the curtain line has to stay clear so it can close.
Do fire curtains need a building permit to install?
Usually they are part of a permitted building or fit-out. Your building surveyor can confirm for your project.
General information, not legal advice. Your building surveyor is the right person to confirm what applies to your building.